CHAPTER 9. BUILDINGS.*
Sec. 9-5.35. Amendments to the California Electrical Code.
The amendments to the California Electrical Code as
referenced in Section 9-5.30 are as follows:
(a) Amend Section 110-26 (C) to read as follows:
Section 110-26 (C) Access and Entrance to Working Space. At
least one entrance of sufficient area shall be provided to give access to the
working space about electric equipment.
For equipment rated 1200 amperes or more and over 6 ft (1.83
m) wide, there shall be one entrance not less than 24 in. (610 mm) wide and 6
1/2 ft. (1.98 m) high at each end of the working space. Where the entrance has a
personnel door(s), the door(s) shall open in the direction of egress and be
equipped with panic bars, pressure plates or other devices that are normally
latched but open under simple pressure.
Exception No 1: Where the location permits a continuous and
unobstructed way of exit travel, one means of access shall be
permitted.
Exception No 2: Where the work space required by Section
110-26(a) is doubled, only one entrance to the working space is required. It
shall be located so the edge of the entrance nearest the equipment is the
minimum clear distance given in Table 110-26(a) away from such
equipment.
(b) Amend Section 210-12 (B) to read as follows:
Section 210-12 (B) Dwelling Unit Bedrooms. All branch
circuits that supply 125-volt, single-phase, 15 and 20-ampere outlets installed
in dwelling unit bedrooms shall be protected by an arc-fault circuit
interrupter(s) listed to provide protection of the entire branch
circuit.
(c) Amend Section 336-4 to read as follows:
Section 336-4 Uses Permitted. Type NM, Type NMC, and Type NMS
cables shall be permitted to be used in the following:
(1) One and Two-Family dwellings.
(2) Multifamily dwellings permitted to be of Types III, IV,
and V construction except as prohibited in 336-5.
(3) Other structures permitted to be of Types III, IV, and V
construction except as prohibited in 336-5. Cables shall be concealed within
walls floors, or ceilings that provide a thermal barrier of material that has at
least a 15-minute finish rating as identified in listings of fire-rated
assemblies.
(4) Cable trays, where the cables are identified for such
use.
(d) Amend Section 625-17 read as follows:
Section 625-17 Cable. The electric vehicle supply equipment
cable shall be Type EV, EVJ, EVE, EVJE, EVT, or EVJT flexible cable as specified
in Article 400 and Table 400.4. Ampacities shall be as specified in Table
400.5(A) for 10 AWG and smaller and Table 400.5(B) for 8 AWG and larger. The
overall length of the cable shall not exceed 7.5 m (25 ft) unless equipped with
a cable management system that is listed as suitable for the purpose. Other
cable types and assemblies listed as being suitable for the purpose, including
optional hybrid communications, signal, and optical fiber cables, shall be
permitted.
(e) Add Article 692 to incorporate current standards for fuel
cell systems as set forth in Resolution Number 18140 adopted by the Salinas City
Council on January 14, 2003 (or by succeeding resolution). (Ord. No. 2276 (NCS),
§ 5; Ord. No. 2410 (NCS) § 1.)